Low pressure switch PS-LA2 -
PCB mounted Air&gas pressure sw -
Vacuum cleaner pressure switch -
Air&gas pressure switch PS-LA7 -
Differential Pressure Switch PS -
Vacuum pressure switch PS-M4V -
Gas Pressure Switch PS-LA12 -
Gas Pressure Switch PS-LA23 -
Gas Pressure Switch PS-LA10-1 -
Low pressure switch PS-LA4 -
Differential Pressure Switch PS -
PCB Mounted Differential Pressu -
Air Pressure Switch PS-LA9 -
Air Pressure Switch PS-LA16 -
Furnace Pressure Switch PS-LA13 -
Low Pressure Switch PS-LA14 -
Low Pressure Switch PS-LA15 -
Vacuum Pressure Switch PS-LA22 -
Low pressure switch PS-LA1 for -
Adjustable differential pressur -
HVAC pressure switch PS-LA8 -
Gas Pressure Switch PS-LA10
HVAC pressure switch PS-LA8
| See more "Air,Gas Pressure Switch" Products
product category: Air,Gas Pressure Switch
Model: PS-LA8
Viewed:
OnLine Service : | |
Print this page | E-mail Us |
Live Messenger | Skype Online |
HVAC pressure switch PS-LA8 are general purpose airflow proving switches designed for HVAC, detection of blocked filters and fan suction, air flow monitoring in ducts, pipes, tunnels, and other energy management applications. It may be used to sense positive, negative or differential air pressure.
The plated housing contain a diaphragm, a calibration spring and a snap-acting switch. The sample connections located on each side of the diaphragm accept a 0.25" OD tubing via the integral compression and nut. An enclosure cover guards against accidental contact with the live switch terminal screws and the set point adjusting screw. The enclosure cover will accept a 0.5" conduit connection. Also, it has a reset button located on the top surface of the enclosure cover.
Model | AFS-222(PS-LA8-1) | AFS-262(PS-LA8-2) | AFS-460(PS-LA8-3) |
Medium | Air | Air | Air |
Mounting Position | Diaphragm in any vertical plane | Diaphragm in any vertical plane | Diaphragm in any vertical plane |
Field Adjustable Range | 0.05±0.02" W.C. to 12.0" W.C. | 0.05±0.02" W.C. to 2.0" W.C. | 0.40±0.06" W.C. to 12.0" W.C. |
Switch Differential | Progressive, increasing from approximately 0.02" W.C at minimum set point, to approximately 0.8" W.C. at maximum set point. | Progressive, increasing from approximately 0.02" W.C at minimum set point, to approximately 0.1" W.C. at maximum set point. | None, Mannual Reset |
Maximum Pressure | 0.5psi (0.03bar) | 0.5psi (0.03bar) | 0.5psi (0.03bar) |
Operating Temperature Range | -40℃-82℃ | -40℃-82℃ | -40℃-82℃ |
Electrical Rating | 300 VA pilot duty at 115-277VAC, 10amp, non-inductive, 277VAC, 60Hz. | 300 VA pilot duty at 115-277VAC, 10amp, non-inductive, 277VAC, 60Hz. | 300 VA pilot duty at 115-277VAC, 10amp, non-inductive, 277VAC, 60Hz. |
Electrical Connections | Screw top terminals with cup washers | Screw top terminals with cup washers | Screw top terminals with cup washers |
Pressure Connections | Ferrule and nut compression type connectors that accept 0.25" OD rigid tubing. | Ferrule and nut compression type connectors that accept 0.25" OD rigid tubing. | Ferrule and nut compression type connectors that accept 0.25" OD rigid tubing. |
Contact type | SPDT | SPDT | 2 SPST-NC (manual reset) |
If you need HVAC pressure switch PS-LA8, please feel free to contact us for price by submitting "more information" as below !
Select by Categories
- Air Compressor Pressure Switch
- Air,Gas Pressure Switch
- Water Pump Pressure Switch
- Multi Medium Pressure Switch
- Pressure Transmitter