Pressure Switch Calibration Procedure


How to Calibrate Pressure Switches
 
Instructions


1.Find out the set point of the pressure switch. The setpoint is the pressure  
  switch's required operating pressure, usually set as a gauge pressure point that
  takes into consideration atmospheric pressure. Some require absolute pressure
  standpoints that work from a pressure point of absolute zero. This is found on
  different places for different models.


2.Investigate the reset or dead-band setting differential. This will tell you how
  much pressure is required to return the switch to its original state, and is
  calculated by the difference in the pressure switch's rising and falling pressures.
  The maximum number the switch is capable of can be found on the nameplate of the  
  switch.


3.Depressurize and isolate the power switch from the rest of the process. Follow all
  safety procedures for the plant you are in. If you are in an environment with 
  explosive gases, monitor the presence of the gases with a continuously monitoring
  gas detector.


4.Attach a hand-pressure regulator and test gauge to the pressure switch. This will
  provide a pressure source from the air supply.


5.Check to see that the switch contacts NO (normally open) and NC (normally close)
  are properly opened or closed. Verify this using a digital multimeter (DMM) or  
  Ohmmeter set to the switch's continuity range.


6.Plug the DMM or Ohmmeter into the NO slot and the common terminal (C) switch and
  make sure the meter reads "open circuit."


7.Add pressure to the pressure switch's setpoint using the hand pressure regulator. Stop when the meter reads "short circuit."

8.Write down the pressure reading on the DMM or Ohmmeter, which is the switch
  setpoint for rising pressure.


9.Add pressure until the meter tells you it has hit its maximum pressure. Then,
  incrementally decrease the pressure until the switch changes back to NO.


10.Copy down the pressure reading, which is the switch setpoint for falling pressure.

11.Subtract the rising pressure from the falling pressure setting. The two readings
   determine the current dead-band of the switch. Compare this number to the
   manufacturer's dead-band. If your number is larger than the manufacturer's, the
   switch is not serviceable.
 